What winter here does to a heat pump
Heat runs November through April here, six months, and the overnight low over December, January and February averages 29°F. That number matters because a standard heat pump starts falling short of its rated heat output below 40°F, and often needs backup heat below about 35°F. Twenty-nine is under both marks. So on a typical winter night here, a standard heat pump is not putting out full heat on its own.
That doesn't mean every night is a struggle. About 90 nights a year here drop to freezing or below, about half the nights in the six months the heat runs. The other half stay above freezing, where a heat pump heats efficiently and backup heat has little to do. And of those 90 cold nights, almost none reach 0°F. This county sees a lot of nights in the 20s and 30s. It almost never sees the deep cold that gives heat pumps real trouble, and field testing of cold-climate models backs that up: even between 0°F and 35°F, backup heat only covered a small share of the load, and running on backup alone was rare above 0°F.
If a heat pump goes into the house, it should carry the ENERGY STAR Cold Climate rating. That designation requires the unit to still make at least 1.75 units of heat per unit of electricity at 5°F, and to hold onto 70 percent of its 47°F capacity at that same temperature. A standard heat pump isn't built or tested to that mark. For a county where the average winter night sits below both the 40°F and 35°F lines, that difference is the one worth paying for.